HomeA/C FINANCINGPackage UnitsQuestionsTestimonialsService & RepairOur EquipmentDuctwork!History of A/CWarranty RegistrtionVALUE ENGINEERINGCommercial HVACPlant CityJob applicationsRequest Estimate

Central air conditioning

Central air conditioning, commonly referred to as central air (U.S.) or air-con (UK), is an air conditioning system which uses ducts to distribute cooled and/or dehumidified air to more than one room, or uses pipes to distribute chilled water to heat exchangers in more than one room, and which is not plugged into a standard electrical outlet.

With a typical split system, the condenser and compressor are located in an outdoor unit; the evaporator is mounted in the air handler unit. With a package system, all components are located in a single outdoor unit that may be located on the ground or roof.

Central air conditioning performs like a regular air conditioner but has several added benefits:

  • When the air handling unit turns on, room air is drawn in from various parts of the building through return-air ducts. This air is pulled through a filter where airborne particles such as dust and lint are removed. Sophisticated filters may remove microscopic pollutants as well. The filtered air is routed to air supply ductwork that carries it back to rooms. Whenever the air conditioner is running, this cycle repeats continually.
  • Because the condenser unit (with its fan and the compressor) is located outside the home, it offers a lower level of indoor noise than a free-standing air conditioning unit.

An Air Conditioner
An air conditioner is a home appliance, system, or mechanism designed to dehumidify and extract heat from an area. The cooling is done using a simple refrigeration cycle. In construction, a complete system of heating, ventilation, and air conditioning is referred to as "HVAC." Its purpose, in a building or an automobile, is to provide comfort during either hot or cold weather.

Air Conditioning

is the dehumidification of indoor air for thermal comfort. In a broader sense, the term can refer to any form of cooling, heating, ventilation, or disinfection that modifies the condition of air.[1] An air conditioner (ofte

n referred to as AC or air con.) is an appliance, system, or machine designed to stabilise the air temperature and humidity within an area (used for cooling as well as heating depending on the air properties at a given time), typically using a refrigeration cycle but sometimes using evaporation, commonly for comfort cooling in buildings and motor vehicles.

The concept of air conditioning is known to have been applied in Ancient Rome, where aqueduct water was circulated through the walls of certain houses to cool them. Similar techniques in medieval Persia involved the use of cisterns and wind towers to cool buildings during the hot season. Modern air conditioning emerged from advances in chemistry during the 19th century, and the first large-scale electrical air conditioning was invented and used in 1902 by Willis Haviland Carrier.

Refrigeration cycle

In the refrigeration cycle, a heat pump transfers heat from a lower-temperature heat source into a higher-temperature heat sink. Heat would naturally flow in the opposite direction. This is the most common type of air conditioning. A refrigerator works in much the same way, as it pumps the heat out of the interior and into the room in which it stands.

This cycle takes advantage of the way phase changes work, where latent heat is released at a constant temperature during a liquid/gas phase change, and where varying the pressure of a pure substance also varies its condensation/boiling point.

The most common refrigeration cycle uses an electric motor to drive a compressor. In an automobile, the compressor is driven by a belt over a pulley, the belt being driven by the engine's crankshaft (similar to the driving of the pulleys for the alternator, power steering, etc.). Whether in a car or building, both use electric fan motors for air circulation. Since evaporation occurs when heat is absorbed, and condensation occurs when heat is released, air conditioners use a compressor to cause pressure changes between two compartments, and actively condense and pump a refrigerant around. A refrigerant is pumped into the cooled compartment (the evaporator coil), where the low pressure causes the refrigerant to evaporate into a vapor, taking heat with it. In the other compartment (the condenser), the refrigerant vapor is compressed and forced through another heat exchange coil, condensing into a liquid, rejecting the heat previously absorbed from the cooled space.

Cylinder unloaders are a method of load control used mainly in commercial air conditioning systems. On a semi-hermetic (or open) compressor, the heads can be fitted with unloaders which remove a portion of the load from the compressor so that it can run better when full cooling is not needed. Unloaders can be electrical or mechanical.

 A Heat Pump

A heat pump is a machine or device that moves heat from one location (the 'source') to another location (the 'sink' or 'heat sink') using mechanical work. Most heat pump technology moves heat from a low temperature heat source to a higher temperature heat sink. Common examples are food refrigerators and freezers, air conditioners, and reversible-cycle heat pumps for providing thermal comfort.

Heat pumps can be thought of as a heat engine which is operating in reverse. One common type of heat pump works by exploiting the physical properties of an evaporating and condensing fluid known as a refrigerant. In heating, ventilation, and air conditioning (HVAC) applications, a heat pump normally refers to a vapor-compression refrigeration device that includes a reversing valve and optimized heat exchangers so that the direction of heat flow may be reversed. Most commonly, heat pumps draw heat from the air or from the ground. Some air-source heat pumps do not work as well when temperatures fall below around −5 °C (23 °F).

When comparing the performance of heat pumps, it is best to avoid the word "efficiency" which has a very specific thermodynamic definition. The term coefficient of performance (COP) is used to describe the ratio of useful heat movement to work input. Most vapor-compression heat pumps utilize electrically powered motors for their work input. However, in most vehicle applications, shaft work, via their internal combustion engines, provide the needed work.

When used for heating a building on a mild day, a typical air-source heat pump has a COP of 3 to 4, whereas a typical electric resistance heater has a COP of 1.0. That is, one joule of electrical energy will cause a resistance heater to produce one joule of useful heat, while under ideal conditions, one joule of electrical energy can cause a heat pump to move much more than one joule of heat from a cooler place to a warmer place.

Note that when there is a wide temperature differential, e.g., when an air-source heat pump is used to heat a house on a very cold winter day, it takes more work to move the same amount of heat indoors than on a mild day. Ultimately, due to Carnot efficiency limits, the heat pump's performance will approach 1.0 as the outdoor-to-indoor temperature difference increases. This typically occurs around −18 °C (0 °F) outdoor temperature for air source heat pumps. Also, as the heat pump takes heat out of the air, some moisture in the outdoor air may condense and possibly freeze on the outdoor heat exchanger. The system must periodically melt this ice. In other words, when it is extremely cold outside, it is simpler, and wears the machine less, to heat using an electric-resistance heater than to strain an air-source heat pump.

Air-source heat pumps

Air source heat pumps are relatively easy (and inexpensive) to install and have therefore historically been the most widely used heat pump type. However, they suffer limitations due to their use of the outside air as a heat source or sink. The higher temperature differential during periods of extreme cold or heat leads to declining efficiency, as explained above. In mild weather, COP may be around 4.0, while at temperatures below around −8 °C (17 °F) an air-source heat pump can achieve a COP of 2.5 or better, which is considerably more than the COP that may be achieved by conventional heating systems. The average COP over seasonal variation is typically 2.5-2.8, with exceptional models able to exceed 6.0 (2.8 kW).

Heating

There are different types of standard heating systems. Central heating is often used in cold climates to heat private houses and public buildings. Such a system contains a boiler, furnace, or heat pump to heat water, steam, or air, all in a central location such as a furnace room in a home or a mechanical room in a large building. The use of water as the heat transfer medium is known as hydronics. The system also contains either ductwork, for forced air systems, or piping to distribute a heated fluid and radiators to transfer this heat to the air. The term radiator in this context is misleading since most heat transfer from the heat exchanger is by convection, not radiation. The radiators may be mounted on walls or buried in the floor to give under-floor heat.

In boiler fed or radiant heating systems, all but the simplest systems have a pump to circulate the water and ensure an equal supply of heat to all the radiators. The heated water can also be fed through another (secondary) heat exchanger inside a storage cylinder to provide hot running water.

Forced air systems send heated air through ductwork. During warm weather the same ductwork can be used for air conditioning. The forced air can also be filtered or put through air cleaners.

Heating can also be provided from electric, or resistance heating using a filament that becomes hot when electric current is caused to pass through it. This type of heat can be found in electric baseboard heaters, portable electric heaters, and as backup or supplemental heating for heat pump (or reverse heating) system.

The heating elements (radiators or vents) should be located in the coldest part of the room, typically next to the windows to minimize condensation and offset the convective air current formed in the room due to the air next to the window becoming negatively buoyant due to the cold glass. Devices that direct vents away from windows to prevent "wasted" heat defeat this design intent. Cold air drafts can contribute significantly to subjectively feeling colder than the average room temperature. Therefore, it is important to control the air leaks from outside in addition to proper design of the heating system.

The invention of central heating is often credited to the ancient Romans, who installed a system of air ducts called a hypocaust in the walls and floors of public baths and private villas.

 HVAC 

HVAC  is an acronym that stands for the closely related functions of "Heating, Ventilating, and Air Conditioning"- the technology of indoor or automotive environmental comfort. HVAC system design is a major subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. Refrigeration is sometimes added to the field's abbreviation as HVAC&R or HVACR, or ventilating is dropped as in HACR (such as the designation of HACR-rated circuit breakers).HVAC is particularly important in the design of medium to large industrial and office buildings such as skyscrapers and in marine environments such as aquariums, where safe and healthy building conditions are regulated with temperature and humidity, as well as "fresh air" from outdoors.

Ventilating

is the process of "changing" or replacing air in any space to control temperature or remove moisture, odors, smoke, heat, dust, airborne bacteria, carbon dioxide, and to replenish oxygen. Ventilation includes both the exchange of air to the outside as well as circulation of air within the building. It is one of the most important factors for maintaining acceptable indoor air quality in buildings. Methods for ventilating a building may be divided into mechanical/forced and natural types. Ventilation is used to remove unpleasant smells and excessive moisture, introduce outside air, and to keep interior building air circulating, to prevent stagnation of the interior air.

 Mechanical or forced ventilation

"Mechanical" or "forced" ventilation is used to control indoor air quality. Excess humidity, odors, and contaminants can often be controlled via dilution or replacement with outside air. However, in humid climates much energy is required to remove excess moisture from ventilation air.

Kitchens and bathrooms typically have mechanical exhaust to control odors and sometimes humidity. Factors in the design of such systems include the flow rate (which is a function of the fan speed and exhaust vent size) and noise level. If the ducting for the fans traverse unheated space (e.g., an attic), the ducting should be insulated as well to prevent condensation on the ducting. Direct drive fans are available for many applications, and can reduce maintenance needs.

Ceiling fans and table/floor fans circulate air within a room for the purpose of reducing the perceived temperature because of evaporation of perspiration on the skin of the occupants. Because hot air rises, ceiling fans may be used to keep a room warmer in the winter by circulating the warm stratified air from the ceiling to the floor. Ceiling fans do not provide ventilation as defined as the introduction of outside air.

 Duct Work

Ducts are used in heating, ventilation, and air conditioning (HVAC) to deliver and remove air. These needed airflows include, for example, supply air, return air, and exhaust air. Ducts also deliver, most commonly as part of the supply air,  As such, air ducts are one method of ensuring acceptable indoor air quality as well as thermal comfort.

A duct system is often called ductwork. Planning ('laying out'), sizing, optimizing, detailing, and finding the pressure losses through a duct system is called duct design.

Polyurethane and Phenolic insulation panels (preinsulated aluminum ducts)

Traditionally, air ductwork is made of sheet metal which is installed first and then lagged with insulation as a secondary operation. Ductwork manufactured from rigid insulation panels does not need any further insulation and is installed in a single fix. Light weight and installation speed are among the features of preinsulated aluminium ductwork, also custom or special shapes of ducts can be easily fabricated in the shop or on site.

The ductwork construction starts with the tracing of the duct outline onto the aluminium preinsulated panel, then the parts are typically cut at 45 degree, bent if required to obtain the different fittings (i.e. elbows, tapers) and finally assembled with glue. Aluminium tape is applied to all seams where the external surface of the aluminium foil has been cut. A variety of flanges are available to suit various installation requirements. All internal joints are sealed with sealant.

Among the various types of rigid polyurethane foam panels available, a new water formulated panel stands out. In this particular panel, the foaming process is obtained through the use of water instead of the CFC, HCFC, HFC and HC gasses. The foam panels are then coated with aluminum sheets on either side, with thicknesses that can vary from 80 micrometres for indoor use to 200 micrometres for external use in order to guarantee the high mechanical characteristics of the duct

A rigid phenolic insulation ductwork system is available and complies with the UL 181 standard for class 1 air ductwork.

Fiberglass duct board (preinsulated non metallic ductwork)

Also the fiberglass panels provide built-in thermal insulation and the interior surface absorbs sound, helping to provide quiet operation of the HVAC system. The duct board is formed by sliding a specially-designed knife along the board using a straightedge as a guide; the knife automatically trims out a "valley" with 45° sides; the valley does not quite penetrate the entire depth of the duct board, providing a thin section that acts as a hinge. The duct board can then be folded along the valleys to produce 90° folds, making the rectangular duct shape in the fabricator's desired size. The duct is then closed with staples and special aluminum or similar 'metal-backed' tape. Commonly available duct tape should not be used on air ducts, metal, fiberglass, or otherwise, that are intended for long-term use; the adhesive on so called 'duct tape' dries and releases with time.

 Flexible Ducting

Flexible ducts, known as flex, have a variety of configurations, but for HVAC applications, they are typically flexible plastic over a metal wire coil to make round, flexible duct. In the United States, the insulation is usually glass wool, but other markets such as Australia, use both polyester fibre and glass wool for thermal insulation. A protective layer surrounds the insulation, and is usually composed of polyethylene or metalised PET. Flexible duct is very convenient for attaching supply air outlets to the rigid ductwork. However, the pressure loss through flex is higher than for most other types of ducts. As such, designers and installers attempt to keep their installed lengths (runs) short, e.g., less than 15 feet or so, and to minimize turns. Kinks in flex must be avoided. Some flexible duct markets prefer to avoid using flexible duct on the return air portions of HVAC systems, however flexible duct can tolerate moderate negative pressures - the UL181 test requires a negative pressure of 200 Pa.[3]

 Fabric

Fabric ducting, also known as air socks, duct socks or textile ducts, are designed for even air distribution throughout the entire length. Usually made of special permeable polyester material, fabric ducts act like a conventional system with much more diffusers.

Fabric ducts are normally used where even air distribution is essential. Due to the nature or the air distribution, textile ducts are not usually concealed within false ceilings, because of this, they are manufactured in various colours to coordinate with the interior.

Fabric ducts fitted above a ceiling will need to be pvc coated so that no maintenance is required to maintain performance.

Because air passes through the body of a textile duct, it is impossible for condensation to form on the ducts surface, they can therefore be used where air is to be supplied below the dew point, without needing to be insulated.

 Zone Dampers

A zone damper (also known as a Volume Control Damper or VCD) is a specific type of damper used to control the flow of air in an HVAC heating or cooling system. In order to improve efficiency and occupant comfort, HVAC systems are commonly divided up into multiple zones. For example, in a house, the main floor may be served by one heating zone while the upstairs bedrooms are served by another. In this way, the heat can be directed principally to the main floor during the day and principally to the bedrooms at night, allowing the unoccupied areas to cool down.

Zone dampers as used in home HVAC systems are usually electrically powered. In large commercial installations, vacuum or compressed air may be used instead. In either case, the motor is usually connected to the damper via a mechanical coupling.

For electrical zone dampers, there are two principal designs.

In one design, the motor is often a small shaded-pole synchronous motor combined with a rotary switch that can disconnect the motor at either of the two stopping points ("damper open" or "damper closed"). In this way, applying power to the "open damper" terminal causes the motor to run until the damper is open while applying power at the "close damper" terminal causes the motor to run until the damper is closed. The motor is commonly powered from the same 24 volt ac power source that is used for the rest of the control system. This allows the zone dampers to be directly controlled by low-voltage thermostats and wired with low-voltage wiring. Because simultaneous closure of all dampers might harm the furnace or air handler, this style of damper is often designed to only obstruct a portion of the air duct, for example, 75%.

Another style of electrically powered damper uses a spring-return mechanism and a shaded-pole synchronous motor. In this case, the damper is normally opened by the force of the spring but can be closed by the force of the motor. Removal of electrical power re-opens the damper. This style of damper is advantageous because it is "fail safe"; if the control to the damper fails, the damper opens and allows air to flow. However, in most applications "fail safe" indicates the damper will close upon loss of power thus preventing the spread of smoke and fire to other areas. These dampers also may allow adjustment of the "closed" position so that they only obstruct, for example, 75% of the air flow when closed.

For vacuum- or pneumatically-operated zone dampers, the thermostat usually switches the pressure or vacuum on or off, causing a spring-loaded rubber diaphragm to move and actuate the damper. As with the second style of electrical zone dampers, these dampers automatically return to the default position without the application of any power, and the default position is usually "open", allowing air to flow. Like the second style of electrical zone damper, these dampers may allow adjustment of the "closed" position.

Highly sophisticated systems may use some form of building automation such as BACnet or LonWorks to control the zone dampers. The dampers may also support positions other than fully open or fully closed and are usually capable of reporting their current position and, often, the temperature and volume of the air flowing past the smart damper.

Regardless of the style of damper employed, the systems are often designed so that when no thermostat is calling for air, all dampers in the system are opened. This allows air to continue to flow while the heat exchanger in a furnace cools down after a heating period completes.

Smoke/Fire Dampers

Smoke and Fire dampers are found in ductwork, where the duct passes through a firewall or firecurtain. Smoke dampers are automated with the use of a mechanical motor often referred to as an Actuator. A probe connected to the motor is installed in the run of duct, and detects smoke within the duct system which has been extracted from a room, or which is being supplied from the AHU (Air Handling Unit) or elsewhere within the run. Once smoke is detected within the duct, the Actuator triggers the motor release and the smoke damper will automatically close until manually re-opened.

You will also find Fire dampers in the same places as smoke dampers, depending on the application of the area after the firewall. Unlike smoke dampers, they are not triggered by any electrical system, which is perfect in the event of an electrical failure where the Smoke dampers would fail to close. A fire damper is held open by a bar crossing the corrigated screen, which will break and allow the damper to close when air in the duct is above a certain temperature. This again will then have to be manually re-opened.

Thermostats

Thermostats control the operation of HVAC systems, turning on the heating or cooling systems to bring the building to the set temperature. Typically the heating and cooling systems have separate control systems (even though they may share a thermostat) so that the temperature is only controlled "one-way." That is, in cold weather, a building that is too hot will not be cooled by the thermostat. Thermostats may also be incorporated into facility energy management systems in which the power utility customer may control the overall energy expenditure. In addition, a growing number of power utilities have made available a device which, when professionally installed, will control or limit the power to an HVAC system during peak use times in order to avoid necessitating the use of rolling blackouts. The customer is given a credit of some sort in exchange, so it is often to the advantage of the consumer to buy the most efficient thermostat possible.

Equipment capacity

Air conditioner equipment power in the U.S. is often described in terms of "tons of refrigeration." A "ton of refrigeration" is defined as the cooling power of one short ton (2000 pounds or 907 kilograms) of ice melting in a 24-hour period. This is equal to 12,000 BTU per hour, or 3517 watts. Residential central air systems are usually from 1 to 5 tons (3 to 20 kilowatts (kW)) in capacity.

The use of electric/compressive air conditioning puts a major demand on the electrical power grid in hot weather, when most units are operating under heavy load. In the aftermath of the 2003 North America blackout locals were asked to keep their air conditioning off. During peak demand, additional power plants must often be brought online, usually expensive peaker plants. A 1995 meta-analysis of various utility studies concluded that the average air conditioner wasted 40% of the input energy. This energy is lost in the form of heat, which must be pumped out. There is a huge opportunity to reduce the need for new power plants and to conserve energy.

In an automobile, the A/C system will use around 5 horsepower (4 kW) of the engine's power.

Refrigerants

"Freon" is a trade name for a family of haloalkane refrigerants manufactured by DuPont and other companies. These refrigerants were commonly used due to their superior stability and safety properties. Unfortunately, evidence has accumulated that these chlorine-bearing refrigerants reach the upper atmosphere when they escape. Once the refrigerant reaches the stratosphere, UV radiation from the Sun cleaves the chlorine-carbon bond, yielding a chlorine radical. These chlorine atoms catalyze the breakdown of ozone into diatomic oxygen, depleting the ozone layer that shields the Earth's surface from strong UV radiation. Each chlorine radical remains active as a catalyst unless it binds with another chlorine radical, forming a stable molecule and breaking the chain reaction. CFC refrigerants is common, but decreasing usage include R-11 and R-12. In light of these environmental concerns, beginning on November 14, 1994, the Environmental Protection Agency has restricted the sale, possession and use of refrigerant to only licensed technicians, per Rules 608 and 609 of the EPA rules and regulations;failure to comply may result in criminal and civil sanctions. Newer and more environmentally-safe refrigerants such as HCFCs (R-22, used in most homes today) and HFCs (R-134a, used in most cars) have replaced most CFC use. HCFCs in turn are being phased out under the Montreal Protocol and replaced by hydrofluorocarbons (HFCs) such as R-410A, which lack chlorine. Carbon Dioxide (R-744) is being rapidly adopted as a refrigerant in Europe and Japan with Volkswagen being one of the first automotive manufacturers to roll out the new systems. R-744 must use higher compression to produce an equivalent cooling effect but has the advantage of being about 10% more efficient as compared to R-134A. R-744 also has a co2 factor of 1

The History of Air Conditioning

While moving heat via machinery to provide air conditioning is a relatively modern invention, the cooling of buildings is not. Wealthy ancient Romans circulated aqueduct water through walls to cool their luxurious houses.

The 2nd century Chinese inventor Ding Huan (fl. 180) of the Han Dynasty invented a rotary fan for air conditioning, with seven wheels 3 m (10 ft) in diameter and manually powered. In 747, Emperor Xuanzong (r. 712–762) of the Tang Dynasty (618–907) had the Cool Hall (Liang Tian) built in the imperial palace, which the Tang Yulin describes as having water-powered fan wheels for air conditioning as well as rising jet streams of water from fountains. During the subsequent Song Dynasty (960–1279), written sources mentioned the air conditioning rotary fan as even more widely used.

Medieval Persia had buildings that used cisterns and wind towers to cool buildings during the hot season: cisterns (large open pools in central courtyards, not underground tanks) collected rain water; wind towers had windows that could catch wind and internal vanes to direct the airflow down into the building, usually over the cistern and out through a downwind cooling tower. Cistern water evaporated, cooling the air in the building. Wind catchers were widely used throughout the medieval Muslim world, where they were used for air conditioning in many cities.

Ventilators were invented in medieval Egypt and were widely used in many houses throughout Cairo during the Middle Ages. These ventilators were later described in detail by Abd al-Latif al-Baghdadi in 1200, who reported that almost every house in Cairo has a ventilator, and that they cost anywhere from 1 to 500 dinars depending on their sizes and shapes. Most ventilators in the city were oriented towards the Qibla, as was the city in general.

In the 1600s Cornelius Drebbel demonstrated "turning Summer into Winter" for James I of England by adding salt to water.

In 1758, Benjamin Franklin and John Hadley, professor of chemistry at Cambridge University, conducted an experiment to explore the principle of evaporation as a means to rapidly cool an object. Franklin and Hadley confirmed that evaporation of highly volatile liquids such as alcohol and ether could be used to drive down the temperature of an object past the freezing point of water. They conducted their experiment with the bulb of a mercury thermometer as their object and with a bellows used to "quicken" the evaporation; they lowered the temperature of the thermometer bulb down to 7°F while the ambient temperature was 65°F. Franklin noted that soon after they passed the freezing point of water (32°F) a thin film of ice formed on the surface of the thermometer's bulb and that the ice mass was about a quarter inch thick when they stopped the experiment upon reaching 7°F. Franklin concluded, "From this experiment, one may see the possibility of freezing a man to death on a warm summer's day".

In 1820, British scientist and inventor Michael Faraday discovered that compressing and liquefying ammonia could chill air when the liquefied ammonia was allowed to evaporate. In 1842, Florida physician John Gorrie used compressor technology to create ice, which he used to cool air for his patients in his hospital in Apalachicola, Florida. He hoped eventually to use his ice-making machine to regulate the temperature of buildings. He even envisioned centralized air conditioning that could cool entire cities. Though his prototype leaked and performed irregularly, Gorrie was granted a patent in 1851 for his ice-making machine. His hopes for its success vanished soon afterwards when his chief financial backer died; Gorrie did not get the money he needed to develop the machine. According to his biographer, Vivian M. Sherlock, he blamed the "Ice King", Frederic Tudor, for his failure, suspecting that Tudor had launched a smear campaign against his invention. Dr. Gorrie died impoverished in 1855 and the idea of air conditioning faded away for 50 years.

In 1902, the first modern electrical air conditioning unit was invented by Willis Haviland Carrier in Buffalo, NY. After graduating from Cornell University, Carrier, a native of Angola, NY, found a job at the Buffalo Forge Company. While at Buffalo Forge, Carrier began experimentation with air conditioning as a way to solve an application problem for the Sackett-Wilhelms Lithographing and Publishing Company in Brooklyn, New York, and the first "air conditioner," designed and built in Buffalo by Carrier, began working 17 July 1902.

Designed to improve manufacturing process control in a printing plant, Carrier's invention controlled not only temperature but also humidity. Carrier used his knowledge of the heating of objects with steam and reversed the process. Instead of sending air through hot coils, he sent it through cold coils (ones filled with cold water). The air blowing over the cold coils cooled the air, and one could thereby control the amount of moisture the colder air could hold. In turn, the humidity in the room could be controlled. The low heat and humidity were to help maintain consistent paper dimensions and ink alignment. Later, Carrier's technology was applied to increase productivity in the workplace, and The Carrier Air Conditioning Company of America was formed to meet rising demand. Over time, air conditioning came to be used to improve comfort in homes and automobiles as well. Residential sales expanded dramatically in the 1950s.

In 1906, Stuart W. Cramer of Charlotte, North Carolina, USA, was exploring ways to add moisture to the air in his textile mill. Cramer coined the term "air conditioning", using it in a patent claim he filed that year as an analogue to "water conditioning", then a well-known process for making textiles easier to process. He combined moisture with ventilation to "condition" and change the air in the factories, controlling the humidity so necessary in textile plants. Willis Carrier adopted the term and incorporated it into the name of his company. This evaporation of water in air, to provide a cooling effect, is now known as evaporative cooling.

The first air conditioners and refrigerators employed toxic or flammable gases like ammonia, methyl chloride, and propane which could result in fatal accidents when they leaked. Thomas Midgley, Jr. created the first chlorofluorocarbon gas, Freon, in 1928.

Freon is a trademark name of DuPont for any Chlorofluorocarbon (CFC), Hydrogenated CFC (HCFC), or Hydrofluorocarbon (HFC) refrigerant, the name of each including a number indicating molecular composition (R-11, R-12, R-22, R-134A). The blend most used in direct-expansion home and building comfort cooling is an HCFC known as R-22. It is to be phased out for use in new equipment by 2010 and completely discontinued by 2020. R-12 was the most common blend used in automobiles in the US until 1994 when most changed to R-134A. R-11 and R-12 are no longer manufactured in the US for this type of application, the only source for air conditioning purchase being the cleaned and purified gas recovered from other air conditioner systems. Several non-ozone depleting refrigerants have been developed as alternatives, including R-410A, invented by Honeywell (formerly AlliedSignal) in Buffalo, NY, and sold under the Genetron (R) AZ-20 name. It was first commercially used by Carrier under the brand name Puron.

Innovation in air conditioning technologies continues, with much recent emphasis placed on energy efficiency, and on improving indoor air quality. Reducing climate change impact is an important area of innovation, because in addition to greenhouse gas emissions associated with energy use, CFCs, HCFCs and HFCs are, themselves, potent greenhouse gases when leaked to the atmosphere. For example, R-22 (also known as HCFC-22) has a global warming potential about 1,800 times higher than CO2. As an alternative to conventional refrigerants, natural alternatives like CO2 (R-744) have been proposed.

Health implications

A poorly maintained air-conditioning system can occasionally promote the growth and spread of microorganisms, such as Legionella pneumophila, the infectious agent responsible for Legionnaires' disease, or thermophilic actinomycetes, but as long as the air conditioner is kept clean these health hazards can be avoided. Conversely, air conditioning, including filtration, humidification, cooling, disinfection, etc., can be used to provide a clean, safe, hypoallergenic atmosphere in hospital operating rooms and other environments where an appropriate atmosphere is critical to patient safety and well-being. Air conditioning can have a positive effect on sufferers of allergies and asthma.

In serious heat waves, air conditioning can save the lives of the elderly. Some local authorities even set up public cooling centers for the benefit of those without air conditioning at home.

Refrigeration

 air conditioning equipment usually reduces the humidity of the air processed by the system. The relatively cold (below the dewpoint) evaporator coil condenses water vapor from the processed air, (much like an ice-cold drink will condense water on the outside of a glass), sending the water to a drain and removing water vapor from the cooled space and lowering the relative humidity. Since humans perspire to provide natural cooling by the evaporation of perspiration from the skin, drier air (up to a point) improves the comfort provided. The comfort air conditioner is designed to create a 40% to 60% relative humidity in the occupied space. In food retailing establishments large open chiller cabinets act as highly effective air dehumidifying units.

A specific type of air conditioner that is used only for dehumidifying is called a dehumidifier. A dehumidifier is different from a regular air conditioner in that both the evaporator and condensor coils are placed in the same air path, and the entire unit is placed in the environment that is intended to be conditioned (in this case dehumidified), rather than requiring the condensor coil to be outdoors. Having the condensor coil in the same air path as the evaporator coil produces warm, dehumidified air. The evaporator (cold) coil is placed first in the air path, dehumidifying the air exactly as a regular air conditioner does. The air next passes over the condensor coil re-warming the now dehumidified air. Note that the terms "condensor coil" and "evaporator coil" do not refer to the behavior of water in the air as it passes over each coil; instead they refer to the phases of the refrigeration cycle. Having the condensor coil in the main air path rather than in a separate, outdoor air path (as in a regular air conditioner) results in two consequences—the output air is warm rather than cold, and the unit is able to be placed anywhere in the environment to be conditioned, without a need to have the condensor outdoors.

 Humidity control

Unlike a regular air conditioner, a dehumidifier will actually heat a room just as an electric heater that draws the same amount of power (watts) as the dehumidifier. A regular air conditioner transfers energy out of the room by means of the condensor coil, which is outside the room (outdoors). This is a thermodynamic system where the room serves as the system and energy is transferred out of the system. Conversely with a dehumidifier, no energy is transferred out of the thermodynamic system (room) because the air conditioning unit (dehumidifier) is entirely inside the room. Therefore all of the power consumed by the dehumidifier is energy that is input into the thermodynamic system (the room), and remains in the room (as heat). In addition, if the condensed water has been removed from the room, the amount of heat needed to boil that water has been added to the room. This is the inverse of adding water to the room with an evaporative cooler.

Dehumidifiers are commonly used in cold, damp climates to prevent mold growth indoors, especially in basements. They are also sometimes used in hot, humid climates for comfort because they reduce the humidity which causes discomfort (just as a regular air conditioner, but without cooling the room).

The engineering of physical and thermodynamic properties of gas-vapor mixtures is named Psychrometrics.

All information on this page is from Wikimedia information sources, The information was gathered as a aid for individuals searching for information about the field we provide services in.

A dehumidifier 

A dehumidifier is mostly a household appliance that reduces the level of humidity in the air, usually for health reasons, as humid air can cause mold and mildew to grow inside homes, which has various health risks. Relative humidity is preferably 30 to 50%. Very high humidity levels are also unpleasant for human beings, can cause condensation and can make it hard to dry laundry or sleep. Higher humidity is also preferred by most insects, including clothes moths, fleas and cockroaches. Dehumidifiers are used in industrial climatic chambers for keeping certain level of humidity.

Energy use

It should be noted that in a thermodynamically closed system, any energy input into the system that is being maintained at a set temperature (which is a standard mode of operation for modern air conditioners) requires that the energy removal rate from the air conditioner increases. This increase has the effect that for each unit of energy input into the system (say to power a light bulb in the closed system) this requires the air conditioner to remove that energy. In order to do that the air conditioner must increase its consumption by the inverse of its efficiency times the input of energy. As an example, presume that inside the closed system a 100 watt light bulb is activated, and the air conditioner has an efficiency of 200%. The air conditioner's energy consumption will increase by 50 watts to compensate for this, thus making the 100 W light bulb use a total of 150 W of energy.

It is typical for air conditioners to operate at "efficiencies" of significantly greater than 100%..However it may be noted that the input (electrical) energy is of higher thermodynamic quality than the output which is basically thermal energy (heat dissipated), See Coefficient of performance.

Insulation 

 Maintaining acceptable temperatures in buildings (by heating and cooling) uses a large proportion of total energy consumption worldwide. When well insulated, usually with fiberglass insulation, a building:

  • is energy-efficient, thus saving the owner money.
  • provides more uniform temperatures throughout the space. There is less temperature gradient both vertically (between ankle height and head height) and horizontally from exterior walls, ceilings and windows to the interior walls, thus producing a more comfortable occupant environment when outside temperatures are extremely cold or hot.
  • has minimal recurring expense. Unlike heating and cooling equipment, insulation is permanent and does not require maintenance, upkeep, or adjustment.

Many forms of thermal insulations also absorb noise and vibration, both coming from the outside and from other rooms inside the building, thus producing a more comfortable occupant environment.

Pipe insulation is also important in buildings for pipes that carry heated or cooled fluids.

Window insulation film can be applied to reduce heat gain in summer and heat loss in winter.

See also weatherization and thermal mass; both describe important methods of saving energy and creating comfort. In industry, energy has to be expended to raise, lower, or maintain the temperature of objects or process fluids. If these are not insulated, this increases the heat energy requirements of a process, and therefore the cost and environmental impact.

Seasonal energy efficiency rating (SEER)

For residential homes, some countries set minimum requirements for energy efficiency. In the United States, the efficiency of air conditioners is often (but not always) rated by the seasonal energy efficiency ratio (SEER)'. The higher the SEER rating, the more energy efficient is the air conditioner. The SEER rating is the BTU of cooling output during its normal annual usage divided by the total electric energy input in watt hours (W·h) during the same period.

SEER = BTU ÷ W·h

this can also be rewritten as:

SEER = (BTU / h) ÷ W, where "W" is the average electrical power in Watts, and (BTU/h) is the rated cooling power.

For example, a 5000 BTU/h air-conditioning unit, with a SEER of 10, would consume 5000/10 = 500 Watts of power on average (assuming 1000 hours of operation during a typical cooling season, i.e., 8 hours per day for 125 days per year)

The electrical energy consumed per year can be calculated as the average power multiplied by the annual operating time:

500 W × 1000 h = 500,000 W·h = 500 kWh

Another method that yields the same result, is to calculate the total annual cooling output:

5000 BTU/h × 1000 h = 5,000,000 BTU

Then, for a SEER of 10, the annual electrical energy usage would be:

5,000,000 BTU ÷ 10 = 500,000 W·h = 500 kWh

SEER is related to the coefficient of performance (COP) commonly used in thermodynamics and also to the Energy Efficiency Ratio (EER). The EER is the efficiency rating for the equipment at a particular pair of external and internal temperatures, while SEER is calculated over a whole range of external temperatures (i.e., the temperature distribution for the geographical location of the SEER test). SEER is unusual in that it is composed of an Imperial unit divided by an SI unit. The COP is a ratio with the same metric units of energy (joules) in both the numerator and denominator. They cancel out, leaving a dimensionless quantity. Formulas for the approximate conversion between SEER and EER or COP are available from the Pacific Gas and Electric Company:

(1)     SEER = EER ÷ 0.9
(2)     SEER = COP x 3.792
(3)     EER = COP x 3.413

From equation (2) above, a SEER of 13 is equivalent to a COP of 3.43, which means that 3.43 units of heat energy are pumped per unit of work energy.

Today, it is rare to see systems rated below SEER 9 in the United States, since older units are being replaced with higher-efficiency units. The United States now requires that residential systems manufactured in 2006 have a minimum SEER rating of 13 (although window-box systems are exempt from this law, so their SEER is still around 10). Substantial energy savings can be obtained from more efficient systems. For example by upgrading from SEER 9 to SEER 13, the power consumption is reduced by 30% (equal to 1 - 9/13). It is claimed that this can result in an energy savings valued at up to US$300 per year (depending on the usage rate and the cost of electricity). In many cases, the lifetime energy savings are likely to surpass the higher initial cost of a high-efficiency unit.

As an example, the annual cost of electric power consumed by a 72,000 BTU/h air conditioning unit operating for 1000 hours per year with a SEER rating of 10 and a power cost of $0.08 per kilowatt hour (kW·h) may be calculated as follows:

unit size, BTU/h × hours per year, h × power cost, $/kW·h ÷ (SEER, BTU/W·h × 1000 W/kW)
(72,000 BTU/h) × (1000 h) × ($0.08/kW·h) ÷ [(10 BTU/W·h) × (1000 W/kW)] = $576.00 annual cost

A common misconception is that the SEER rating system also applies to heating systems. However, SEER ratings only apply to air conditioning.

Air conditioners (for cooling) and heat pumps (for heating) both work similarly in that heat is transferred or "pumped" from a cooler heat source to a warmer "heat sink". Air conditioners and heat pumps usually operate most effectively at temperatures around 10 to 13 degrees Celsius (°C) (50 to 55 degrees Fahrenheit (°F)). A balance point is reached when the heat source temperature falls below about 4 °C (40 °F), and the system is not able to pull any more heat from the heat source (this point varies from heat pump to heat pump). Similarly, when the heat sink temperature rises to about 49 °C (120 °F), the system will operate less effectively, and will not be able to "push" out any more heat. Geothermal heat pumps do not have this problem of reaching a balance point because they use the ground as a heat source/heat sink and the ground's thermal inertia prevents it from becoming too cold or too warm when moving heat from or to it. The ground's temperature does not vary nearly as much over a year as that of the air above it.

References
  1. ^ ASHRAE Terminology of HVAC&R, ASHRAE, Inc., Atlanta, 1991,
  2. ^ Needham, Joseph (1986). Science and Civilization: Volume 4, Physics and Physical Technology, Part 2, Mechanical Engineering. Taipei: Caves Books Ltd. Pages 99, 151, 233.
  3. ^ Needham, Joseph (1986). Science and Civilization: Volume 4, Physics and Physical Technology, Part 2, Mechanical Engineering. Taipei: Caves Books Ltd. Pages 134 & 151.
  4. ^ Needham, Joseph (1986). Science and Civilization: Volume 4, Physics and Physical Technology, Part 2, Mechanical Engineering. Taipei: Caves Books Ltd. Page 151.
  5. ^ Ancient air conditioning, The World, January 11, 2007
  6. ^ Lindsay, James E. (2005), Daily Life in the Medieval Islamic World, Greenwood Publishing Group, p. 127, ISBN 0313322708 
  7. ^ David A. King (1984). "Architecture and Astronomy: The Ventilators of Medieval Cairo and Their Secrets", Journal of the American Oriental Society 104 (1), p. 97-133.
  8. ^ Laszlo, Pierre. Salt. http://books.google.com/books?id=DhhN_FthpYMC&pg=PA117&dq=Cornelius+Drebbel+%22air+conditioning%22&ei=nw6bScXrM4TMlQTChJXmCQ. 
  9. ^ Cooling by Evaporation (Letter to John Lining). Benjamin Franklin, London, June 17, 1758
  10. ^ History of Air Conditioning Source: Jones Jr., Malcolm. "Air Conditioning". Newsweek. Winter 1997 v130 n24-A p42(2). Retrieved 1 January 2007.
  11. ^ The History of Air Conditioning Lou Kren, Properties Magazine Inc. Retrieved 1 January 2007.
  12. ^ IPCC Fourth Assessment Report, Table 2.14
  13. ^ The current status in Air Conditioning - papers & presentations
  14. ^ Sick building syndrome
  15. ^ Home Control of Asthma & Allergies
  16. ^ Jan F. Kreider. Handbook of heating, ventilation, and air conditioning. CRC press. ISBN ISBN 0849395844. 
  17. ^ Winnick, J (1996). Chemical engineering thermodynamics. John Wiley and Sons. ISBN 0471055905. 
  18. ^ Michigan Fast Facts and Trivia, retrieved on 2009-08-29.
  19. ^ a b "Air Conditioning and Refrigeration Timeline", National Academy of Engineering, retrieved 2009-08-29.
  20. ^ "Air Conditioning and Refrigeration History - part 4", National Academy of Engineering, retrieved 2009-08-29.
  21. ^ Alder, Dennis (2004). Packard. MBI Publishing Company. p. 76. ISBN 9780760319284. 
  22. ^ The Great Lakelands (Lake Valley, Inc) 6: 32. 1956. 
  23. ^ Gunnell, John (1982). Standard catalog of American cars, 1946-1975. Krause Publications. p. 176. 
  24. ^ a b Al Binder and the Ward's staff, "Rearview Mirror", Ward's AutoWorld, 2001-02-01, retrieved on 2009-08-26.
  25. ^ Daly, Steven (2006). Automotive Air-Conditioning and Climate Control Systems. Elsevier Science & Technology Books. p. 2. ISBN 9780750669559. 
  26. ^ Stevenson, Heon J. (2008). American Automobile Advertising, 1930-1980: An Illustrated History. McFarland & Company. p. 177. ISBN 9780786436859. 
  27. ^ "1953-1955 Nash and Hudson Ramblers" by the editors of Consumer Guide, 2007-11-29, retrieved on 2009-08-29.
  28. ^ Nunney, Malcolm J. (2006). Light and Heavy Vehicle Technology. Elsevier Science & Technology Books. p. 147. ISBN 9780750680370. 
  29. ^ Nash, Gerald D. (1999). Federal Landscape: An Economic History of the Twentieth-Century West. University of Arizona Press. pp. 224. ISBN 9780816518630. 
  30. ^ Ward's automotive yearbook (Ward's Communications Inc.) 31: 116. 1969. 
  31. ^ "U.S. Business: Shuffle & Cut", Time, October 6, http://www.time.com/time/printout/0,8816,844040,00.html 
  32. ^ ACCA home page